Universal Hotwater Boilers

TKU-E boilers are flue fire-tube, two-tensile, large-capacity boilers determined for the combustion of liquid and gaseous fuels. The combustion chamber size is designed so as to minimize emissions. The design pressure of KU line boilers is 0,6; 1,0 or 1,6 MPa. The boilers are supplied on a standard frame, including insulation with sheeting and a service platform. The supply includes the respective fittings. The boilers are equipped with economizers (eco). It is possible to place behind the boiler condensate exchangers, which utilizes the vapour heat included in the flue gas. The design, manufacturing, testing and additional equipment of boilers are done according to the CSN technical standards.

Standard boiler equipment:

  • Safety valve - 2x
  • Closing valve - water inlet DN 250 - 1 x
  • Closing valve - water outlet DN 250 - 1x
  • Air relieve valve DN 40 - 1x
  • Intermittent blowdown valve DN 40 - 1x
  • Manometer - 1x
  • Thermometer measuring on water piping inlet - 1x
  • Thermometer measuring on water piping outlet - 1x
  • Thermometer for outlet flue gas measuring - 1x
  • Manometer for water pressure (min.,max.) - 2x
  • Temperature sensor (max. outlet water temperature) - 1x
  • Thermostat (min. inlet water temperature) - 1x
  • Emergency thermostat max. outlet water temperature - 1x

 

Technical Parameters - TKU 6000-E

Parameters Units         TKU 6000-E          
Rated thermal capacity kW 6000
Maximum thermal capacity kW 6600
Maximum overpressure MPa (0,6 ; 1,0 ; 1,6)
Minimum steam overpressure** MPa 0,2 - 0,4
Nominal temperature of superheated steam* % 92
Efficiency - with eco % 96
Flue gas temperature - boiler without eco °C 180
Flue gas temperature - boiler with eco °C  
Minimum temperature of circulated water-inlet °C 60
Maximum outlet temperature of water °C 110
Minimum allowed temperature drop of circulated water °C 10
Temperature of sucked air °C 20
Maximum fuel consumption - natural gas Nm3/hr 759
Amount of combusted air (lambda=1,1) Nm3/hr 8045
Amount of flue gases Nm3/hr 8880
Overpressure in the furnace - boiler without eco Pa 650
Overpressure in the furnace - boiler with eco Pa 150
Middle volume load of combustion chamber MW/Nm3 1,1
Water volume of boiler m3 8,6
Water volume of eco with connecting piping m3 0,5
Heating surface of boiler m2 176
Heating surface of eco m2 277,6
Noise level dB Max.80
Emissions***
Natural gas mg/Nm3 NOx - 100 
CO - 100
KU Boiler weight
Boiler weight kg 18600
Eco weight kg 2400
Boiler operating weight kg 30 850
Boiler dimensions
Boiler length mm 6500
Boiler width mm 2300
Boiler width with eco mm 2400
Boiler height without eco mm 2460
Boiler height with eco mm 3750
Diameter of flue gas branch mm 700
Diameter of inlet and outlet water branch   DN 250
Safety branch   2xDN80
Intermittent blowdown branch   DN 50
Eco drainage branch   G1“
Condensate outlet branch   G1“
Assembly hole - boiler without eco mm 2,6 x 3
Assembly hole - boiler with eco mm 2,6 x 3,7
Space on right side (in direction from burner) mm 600
Space on left side (in direction from burner) mm 1200
Space behind boiler mm 800
Space in front of boiler 
Possible to put gate or make assembly hole
mm 5000

*** Emissions relate to 3% O2 in dry combustion products at t = 0°C and barometric pressure.